Provide guidelines and procedures for working on energized equipment and systems, including testing, troubleshooting, and voltage measurement.
The electrical system at the university is a complex network of power generation, distribution, and premises systems.
This policy applies to work performed at NC State on equipment associated with premises systems, which is designed in accordance with the National Fire Protection Association standard NFPA 70, National Electrical Code (NEC®). Premises systems typically begin at the service point, service entry, or the service meter.
This policy does not apply to work performed at NC State on power generation, transmission, and distribution systems designed in accordance with the Institute of Electrical and Electronics Engineers (IEEE) National Electrical Safety Code (NESC®). Power generation, transmission, and distribution typically ends at the service point, service entry, or the service meter of the building or premises.
2.0 Introduction
2.1 NC State’s goal is to minimize employee exposure to shock and arc flash hazards that can occur during the installation, repair, maintenance, and operation of electrical equipment, components, and systems. Electrical power sources shall be de-energized and verified prior to working on electrical equipment except when de-energization creates a greater hazard and a properly executed and approved Energized Electrical Work Permit (EWP) has been completed.
2.2 This policy outlines the minimum guidelines for:
3.0 Definitions
The following terms are defined to allow a better understanding of this program. For more detailed definitions, refer to 2018 NFPA 70E, Article 100.
An arc flash risk assessment is a process to determine if an arc flash hazard exists. If it does, the risk assessment shall determine the appropriate safety-related work practices, the arc flash boundary, and the personal protective equipment (PPE) to be used within the arc flash boundary.
A complete AR (Arc-Rated) clothing and equipment system that covers the entire body, except for the hands and feet.
Apparel is a broad category of clothing designed to protect employees from electrical arc events during completion of energized tasks. (Such a suit typically includes pants, jacket, and a “beekeeper” style hood fitted with a face shield). (see NFPA 70E 130.7(C))
Note: Protective apparel for other body parts, including hands, feet, and hearing is also required. [See Section 7.0], “Electrical Personal Protective Equipment.”
The maximum incident energy resistance demonstrated by a material (or a layered system of materials) prior to “breaking open” or at the onset of a second-degree skin burn. This rating is assigned to electrical protective clothing and is normally expressed in calories per square centimeter (cal/cm2).
Note: An arc rating indicates the clothing or equipment has been tested for protection against exposure to an electric arc. Flame resistant clothing, without an arc rating, has not been tested for exposure to an electric arc. (see 2018 NFPA 70E-100)
A distance from an electrical device or system used to specify what activities are allowed, and what personal protective equipment is required within that distance from the electrical device or system.
There are two boundary categories: the arc flash boundary and the shock protection boundaries. There are two levels of shock protection boundaries: limited approach boundary and restricted approach boundary.
Distance from exposed live parts within which a person could receive a second-degree burn if an electrical arc flash were to occur. This boundary may only be crossed by a qualified person wearing the appropriate personal protective equipment (PPE).
The shock protection boundaries identified as limited approach boundary and restricted approach boundary shall be applicable where approaching personnel are exposed to energized electrical conductors or circuit parts.
The distance from an exposed energized electrical conductor or circuit part within which a shock hazard exists.
The distance from an exposed energized electrical conductor or circuit part within which there is an increased likelihood of electric shock, due to electrical arc-over combined with inadvertent movement, for personnel working in close proximity to the energized electrical conductor or circuit part.
(De-energized): Free from any electrical connection to a source of potential difference and from electrical charge; not having a potential different from that of the earth.
A state in which an electrical conductor or circuit part has been disconnected from energized parts, locked/tagged in accordance with NCSU policy, tested to ensure the absence of voltage, and grounded if determined necessary.
Electrically connected to, or is, a source of voltage.
Capable of being inadvertently touched or approached nearer than a safe distance by a person. It is applied to electrical conductors or circuit parts that are not suitably guarded, isolated, or insulated.
A source of possible injury or damage to health.
Involving exposure to at least one hazard.
The amount of thermal energy impressed on a surface, a certain distance from the source, generated during an electrical arc event. Incident energy is typically expressed in calories per square centimeter (cal/cm2) at a specified distance.
Energized conductive components.
Activities which promote the operation or extend the life of equipment or systems.
An acronym for “Personal Protective Equipment”.
One who has demonstrated the skills and knowledge related to the construction and operation of electrical equipment and installations and has received safety training to identify and avoid the hazards involved. [See Section 5.0] Training
A person who is not a qualified person. A person who has not received safety training or who has not demonstrated the skills and knowledge related to the construction and operation of electrical equipment and installations.
The distance from the source/origin of a potential arc flash and the plane defined by the employee’s face and chest. Note: The working distance as defined by the table method is fixed, whereas it can vary when the incident energy method is employed [Section 8.2] Arc Flash Risk Assessment Methodology .
Any activity within a limited approach boundary.
Intentionally coming in contact with energized electrical conductors or circuit parts with the hands, feet, or other body parts, with tools, probes, or with test equipment, regardless of the personal protective equipment (PPE) a person is wearing.
There are two categories of “working on”:
Diagnostic (testing) is taking readings or measurements of electrical equipment with approved test equipment that does not require making any physical change to the equipment.
Repair is any physical alteration of electrical equipment (such as making or tightening connections, removing or replacing components, etc.).
4.0 Approach Boundaries to Live Parts
Observing a safe approach distance from exposed energized parts is an effective means of maintaining electrical safety. As the distance between an individual and live parts increases, the potential for an electrical injury decreases. Safe approach distances will be determined for all tasks in which approaching personnel are exposed to live parts. For shock hazards, safe approach distances to fixed live parts can be determined by referring to mandatory Appendix A, “Shock Protection Approach Boundaries.” This appendix must be used to identify the limited and restricted approach boundaries associated with various system voltages.
The arc flash boundary is determined by an Arc Flash Risk Assessment and is based on several system attributes in addition to voltage. Refer to Section 4.3 and Section 8.0, below.
Barricades shall be used in conjunction with safety signs, where necessary, to prevent or limit employee access to work areas containing energized conductors or circuit parts. Conductive barricades shall not be used where it might increase the likelihood of exposure to an electrical hazard. Barricades shall be placed no closer than the applicable limited approach boundary given in Appendix A, (ref. 2018 NFPA 70E Table 130.4 (D)(a) or Table 130.4(D)(b)). Where the arc flash boundary is different than the limited approach boundary, barricades shall be placed at the farther boundary.
4.1 Limited Approach Boundary
No unqualified person shall be permitted to approach nearer than the limited approach boundary of energized conductors and circuit parts unless a qualified person advises him or her of the possible hazards and continuously escorts the unqualified person while inside the limited approach boundary. Where one or more unqualified persons are working at or close to the limited approach boundary, the person in charge of the workspace where the electrical hazard exists shall advise the unqualified persons of the electrical hazards and warn him or her to stay outside of the limited approach boundary.
4.2 Restricted Approach Boundary
Qualified persons shall not approach or take any conductive object closer to exposed energized electrical conductors or circuit parts operating at 50 volts or more into the restricted approach boundary unless one of the following conditions apply:
Note: An EWP is not required for troubleshooting, testing, voltage measurement, or visual observation.
Under no circumstance shall an unqualified person be permitted to cross the restricted approach boundary.
4.3 Arc Flash Boundary
The arc flash boundary is the distance from exposed live parts within which a person could receive a second-degree burn (1.2 cal/cm 2 ) if an electrical arc flash were to occur. This boundary may only be crossed by a qualified person wearing the appropriate personal protective equipment (PPE).
To determine the arc flash boundary, an Arc Flash Risk Assessment [Section 8.0] must be done, using the Incident Energy (IE) Analysis Method. If the equipment has not had an IE analysis, the user should contact EHS for assistance, env-health-occ-safety@ncsu.edu, 919-515-6655.
The arc flash boundary may also be determined using the “Table Method;” provided the following requirements are met:
5.0 Training (derived from 2018 NFPA 70E, 110.2)
5.1 Employees exposed to an electrical hazard must receive electrical safety training based on the level of the hazard and dependent on the work being done. A qualified person will receive more training than an unqualified person.
Note: A person can be considered qualified with respect to certain equipment and tasks but not qualified for other equipment or tasks.
5.2 All employees exposed to actual or potential electrical hazards are required to have training to include:
5.3 Only qualified persons are authorized to perform energized work.
6.0 Responsibilities
6.1 All Departments conducting electrical work
6.2 Departments responsible for operating and maintaining electrical equipment
(For Example: Building Maintenance and Operations in Facilities Division and Facilities units in DASA, Athletics, and Campus Enterprises)
6.3 Supervisors, Superintendents, PIs, Managers
6.4 Employees
6.5 Contract Employers
7.0 Electrical Personal Protective Equipment
7.1 Electrical PPE requirements are described in a separate program titled “Electrical Personal Protective Equipment” and shall be followed by all NCSU employees. Contact EHS Occupational Safety, Env-Health-Occ-Safety@ncsu.edu, 919-515-6655, for assistance.
8.0 Arc Flash Risk Assessment
8.1 Overview The 2018 edition of NFPA 70E requires analysis of incident energy or arc flash PPE category for determination of arc flash hazards, and specifies the following:
8.2 Arc Flash Risk Assessment Methodology There are two methods for determining the approach distances (arc flash boundary) and the arc rated PPE required for energized work: the Incident Energy (IE) Analysis Method and the Arc Flash Categories Method (Table Method). The IE method is preferred. The two methods shall not be combined.
The equipment to be worked on must exactly match the equipment described in the table. Based upon the short-circuit current available and the fault clearing time, the required arc flash PPE category and the arc-flash boundary are then read from the table. If all parameters in the table are not met, this method shall not be used and therefore, the Incident Energy Analysis method is required. Contact EHS Occupational Safety, Env-Health-Occ-Safety@ncsu.edu, 919-515-6655, if there are questions.
The table method can be inaccurate and, while generally conservative, the maximum potential energy of some equipment may be greater than the PPE category determined by the table. The Incident Energy Analysis Method is preferred.
9.0 Operating Procedures – Energized Work
9.1 Appendix E, “Electrical Work Decision Flow Chart” can be used as guidance for doing safe electrical work.
9.2 Energized parts to which an employee may be exposed shall be de-energized before the employee works on or near them.
9.3 At no time shall any employee perform work alone on energized equipment. Only employees qualified for the task may work on or near energized equipment.
9.4 Energized parts that operate at less than 50 volts to ground need not be de-energized if there will be no increased exposure to electrical shock or burns or to explosion due to electric arcs.
9.5 Some diagnostic work must be done energized. Every effort should be made, where possible, to work without coming in physical contact with electrical conductors or circuit parts. Refer to Section 9.7(A) for information on energized diagnostic work.
9.6 Repair work must be done de-energized unless the qualified person can justify working energized using one or more of the criteria specified in Section 10.0. Where the qualified person is closer than the arc flash or restricted approach boundary, An energized work permit, Section 11.0, must be used. An energized work permit is not required for repair work done remotely.
9.7 Working On or Near Energized Parts (refer to definition in Section 3.0, above)
9.8 On-Call or After Hours Operations involving energized work.
10.0 Justification for energized electrical work:
10.1 Only these criteria may be used to justify doing energized repair work.
11.0 Energized Electrical Work Permit (EEWP/EWP), mandatory Appendix D
11.1 Determine the arc flash hazard (See Section 8.0).
11.2 Determine the justification for conducting work energized (See Section 10.0).
11.3 Obtain management approval to proceed.
11.4 Establish approach and arc flash boundaries, according to 2018 NFPA 70E.
11.5 Erect barricades and signage to prevent personnel from entering the area of the hazard.
11.6 Use insulated tools and equipment.
11.7 Use insulated mats when required.
11.8 Determine and wear the required PPE.
11.9 Wear safety glasses and hearing protection.
11.10 Wear electrical shock protective PPE, including, but not necessarily limited to, voltage rated gloves, safety glasses, ear insert hearing protectors, EH rated hard-soled leather work shoes.
11.11 Wear appropriate AR upper and lower body personal protective equipment (Mandatory Appendix B or Appendix C, and 2018 NFPA 70E Annex H).
11.12 The permit is to be originated by the individual requesting the energized work. (This may be the qualified technician responsible for the operation and maintenance of the building systems, a supervisor, or a project manager.)
11.13 All Energized Electrical Work Permits shall be submitted to the appropriate supervisor for approval.
11.14 The permit must be posted in the area where the energized work is taking place for the duration of the task.
11.15 Energized Electrical Work Permits must be kept (with a copy of the work order(s), as appropriate) on file by the supervisor upon completion of the task. Permits shall be kept for a minimum of three years in order to be used as part of the audit process.
11.16 A copy of the NCSU Energized Electrical Work Permit can be found in mandatory Appendix D of this Policy. The intent of this permit is to ensure that all appropriate safety precautions are taken prior to starting energized electrical work and to ensure oversight by supervisors in the area the work is being performed.
12.0 Appendix E, the “Electrical Work Decision Flow Chart” can be used as guidance for doing safe electrical work.